DATA SHEET:
The LCU032 Series temperature/process controls The LCU032 offers universal input (13 thermocouple scales, 2 RTD types,
voltage, and current), universal single set point with alarm, or heat / cool
output. Standard features include Fuzzy Logic and Self-tune. Process protection
is provided by open sensor protection and shorted sensor protection. The LCU032 can be used as an indicator and the proportional current output
programmed as a process retransmission output. For the cost of a panel
meter alone, you can have a panel meter with process retransmission, or a full
blown PID process control The LCU032 family of controls offers the greatest value with high levels of features,
function, and quality available today.
Standard Features
• Large Single display
• Self-Tune / Fuzzy logic
• Universal input
• Universal Output
• IP65 (NEMA 4X) Front Panel
SpecificationsSelectable Inputs: (See
range chart) Input Impedance: Sample Time: 250mS. Sensor Break Protection: Upscale or downscale for thermocouples, upscale only for RTD. Set Point Range: Selectable (See range chart) Display: One 4 digit, 7 segment LED. Control Action: Reverse (usually heating), Direct (usually cooling) selectable. Proportional Band: 0.1 to 999.9% of full scale. Reset Time (Integral): Off or 1 to 6000 seconds. Rate Time (Derivative): Off or 1 to 6000 seconds. Cycle Rate: 1 to 80 seconds. On-Off Differential: Adjustable 0.0 to 100% of full scale. Alarm On-Off Differential: Adjustable 0.0 to 100% of full scale. Fuzzy Logic: On or Off. Accuracy: ±0.5% of span, ±1 least significant digit. Resolution: 1 count or 1 degree or 0.1 degree per range. Temperature Stability: 100 ppm/°C typical, 200 ppm/°C max. Reference Junction Accuracy: ±1.5°C @ 15 to 35°C, ±2.0°C 0 to 50° C Supply Voltage: 100 to 240 VAC 50/60 Hz. Power Consumption: 10 VA maximum. Operating Temperature: -0 to +50 °C (+32 to 131 °F). Storage Temperature: -25 to +70 °C (-40 to 176 °F). Humidity Conditions: 20 to 90% non-condensing. Memory Backup: Nonvolatile memory. No batteries required. Control Output Ratings: SSR Drive (non-isolated): 24 VDC @ 20 mA (max load 600 ohms). Relay: SPST, 1 A @ 240 VAC resistive. Current (non-isolated): 4 to 20 mA across 600 ohms max. Panel Cutout: 45 mm x 22 mm (1.775" x 0.874"). Depth Behind Mounting Surface: 100 mm (3.94"). Weight: 114 g (4 oz). Agency Approvals: CE, UL E83725. Front Panel Rating: IP65 (Type 4X). Communications Option: Standard: RS-485 Address Range: 1 to 99. Connection: 2-wire, Half Duplex Communications Rate: Selectable, 600, 1200, 2400, 4800, 9600 Baud. Start Bit: 1. Data Bits: 7 or 8, programmable. Parity Bit: None, even, or odd, programmable. Stop Bit: 1 or 2, programmable. Protocol: Modbus, ASCII or RTU, programmable. Response Time: 10 to 100mS, programmable. |
All dimensions in millimeters (inches)

Input Ranges
| Input Type | Range °F | Range °C |
| Type J Thermocouple | -300 to +2300 | -199.9 to +999.9 |
| Type K Thermocouple | -300 to +2500 | -200 to +1370 |
| Type K Thermocouple | 0 to 2300 | -199.9 to +999.9 |
| Type T Thermocouple | -300 to +750 | -199.9 to +400.0 |
| Type E Thermocouple | -300 to +1800 | -199.9 to +999.9 |
| Type L Thermocouple | -300 to +1300 | -199.9 to +900.0 |
| Type R Thermocouple | 32 to 3100 | 0 to +1700 |
| Type S Thermocouple | 32 to 3100 | 0 to +1700 |
| Type B Thermocouple | +32 to +3300 | 0 to +1800 |
| Type N Thermocouple | -300 to +2400 | -200 to +1300 |
| Type U Thermocouple | -300 to +750 | -199.9 to +400.0 |
| Type W Thermocouple | 32 to 4200 | 0 to 2300 |
| Platinel II | 32 to 2500 | 0 to 1390 |
| 100 ohm Plt. 0.00385 DIN RTD | -328 to 1607 | -200 to +875 |
| 100 ohm Plt. 0.00392 NIST RTD | -328 to 1607 | -200 to +875 |
| 1 to 5 V* | Scalable Units from -1999 to +9999 | |
| -10 to +20 mV* | Scalable Units from -1999 to +9999 | |
| 0 to 100 mV* | Scalable Units from -1999 to +9999 | |
| 4 to 20 mA* | Scalable Units from -1999 to +9999 | |
* These inputs are fully scalable from a minimum of 100 counts span placed anywhere within the within the range of -1999 to +9999. Decimal point position is adjustable from the zero place (9999), tenths (999.9), hundredths (99.99), thousandths (9.999), or ten thousandths (.9999).
MODEL IDENTIFICATION
To order, specify part number as shown below.
MODEL NUMBER - OUTPUT /
OPTIONS
LCU032 - 00 = Universal / None
LCU032 - 01 = Universal / RS-485 Communications
LCU032 - 10 = Heat-Cool / None
HOW TO ORDER:
LCU032-00: Temperature Controller, Universal Input, Universal Single Setpoint with Alarm Output.... $160.00
LCU032-01: Temperature Controller, Universal Input, Universal Single Setpoint with Alarm Output, RS485 COM....$210.00
LCU032-10: Temperature Controller, Universal Input, Heat or Cool Output.... $210.00
LCU032 Instruction and Operation Manual