Automated Aquarium Systems

Portable Temperature Process Controller


Love 986
Dimensional Image


DATA SHEET:

The 986 Option portable housing allows use of either of these popular and powerful 1/4 DIN controls as a portable or bench top control. Designed for rugged use, the 986 option allows operation on any standard US 3-prong outlet.


Features

  • 10 Amp 120 VAC outlet on front panel
  • On-off switch with pilot lamp
  • Combination jack for standard or mini size thermocouple plugs
  • Self storing 4 foot power cord
  • Optional alarm has audible signal with volume control

Specifications

  • Selectable Inputs: Thermocouple, RTD, DC Voltage, or DC Current selectable.
  • Input Impedance: Thermocouple = 3 megohms minimum. RTD current = 200 µA.
  • Current = 10 ohms. Voltage = 5000 ohms.
  • Sensor Break Protection: User determines control output to protect system after customer set time.
  • Set Point Range: Selectable (See Range Chart, previous page).
  • Display: Two 4 digit, 7 segment 0.30" high LEDs.
  • Control Action: Reverse (usually heating), Direct (usually cooling) selectable.
  • Proportional Band: 1 to 9999 °F, °C, or counts.
  • Reset Time (Integral): Off or 0.1 to 99.9 minutes.
  • Rate Time (Derivative): Off or 0.01 to 99.99 minutes.
  • Cycle Rate: 1 to 80 seconds.
  • On - Off Differential: Adjustable 1° F, 1° C, or 1 count to full scale in 1° F, 1° C, or 1 count steps.
  • Alarm On - Off Differential: 1° F, 1° C, or 1 count.
  • Fuzzy Intensity: 0 to 100%.
  • Fuzzy Rate: Off or 0.01 to 99.99 minutes.
  • Fuzzy Band: Off or 1 to 4000 °F, °C, or counts.
  • Accuracy: ±0.25% of span, ±1 least significant digit.
  • Resolution: 1 degree or 0.1 degree, selectable.
  • Line Voltage Stability: ±0.05% over the supply voltage range.
  • Temperature Stability: 4µV/°C (2.3 µV/°F) typical, 8 µV/°C (4.5 µV°F) maximum (100 ppm / °C typical,
  • 200 ppm / °C maximum).
  • Common Mode Rejection: 140 db minimum at 60 Hz.
  • Normal Mode Rejection: 65 db typical, 60 db at 60 Hz.
  • Isolation: Relay and SSR outputs: 1500 VAC to all other inputs and outputs.
  • SP1 and SP2 Current outputs: 500 VAC to all other inputs and outputs, but not isolated from each other.
  • SP1 and SP2 Switched Voltage outputs: 500 VAC to all other inputs and outputs, but not isolated from each other.
  • Process Output (Options 934, 936): 500 VAC to all other inputs and outputs.
  • Supply Voltage: 100 to 240 VAC, nominal., +10 -15%, 50 to 400 Hz. single phase; 132 to 240 VDC, nominal., +10 -20%.
  • Power Consumption: 5VA maximum.
  • Operating Temperature: -10 to +55 °C (+14 to 131 °F).
  • Storage Temperature: -40 to +80 °C (-40 to 176 °F).
  • Humidity Conditions: 0 to 90% up to 40 °C non-condensing 10 to 50% at 55 °C non-condensing.
  • Memory Backup: Nonvolatile memory. No batteries required.
  • Control Output Ratings:
  • SSR: 2.0 A combined outputs A & B @ 240 VAC at 25 °C (77°F). Derates to 1.0 A @ 55° C (130°F).
  • Relay: SPDT, 3 A @ 240 VAC resistive; 1.5 A @ 240 VAC inductive;Pilot Duty Rating: 250 VA, 2 A
  • @ 120 VAC or 1 A @ 240 VAC.
  • Alarm Relay: SPST, 3 A @ 240 VAC resistive; 1.5 A @ 240 VAC inductive; Pilot Duty Rating: 240
  • VA, 2 A @ 120 VAC or 1 A @ 240 VAC.
  • Current (isolated): 0 to 20 mA across 600 ohms maximum.
  • Switched Voltage (isolated): 15 VDC @ 20 mA.
  • Panel Cutout: 45 mm x 45 mm (1.775" x 1.775").
  • Depth Behind Mounting Surface: 115.3 mm (4.54").
  • Weight: 227 g (8 oz).
  • Agency Approvals: Pending.
  • Front Panel Rating: Type 4X, (IP65).

Input Ranges

Specify by Order Code

INPUT TYPE RANGE  Order Code
T/C, J*, Iron/Constantan -100 to 1600° F
-73 to 871° C
986/J
T/C, K* -200 to 2500° F
-129 to 1371° C
986/K
RTD, 100 Ohm Platinum, 0.00392 Ohms/Ohm/°C* -328 to 1607° F
-200 to 875° C
986/RTD
RTD, 120 Ohm Nickel, 0.006725 Ohms/Ohm/°C* -112 to 608° F
-80 to 320° C
986/RTD
RTD, 100 Ohm Platinum, 0.00385 Ohms/Ohm/°C* -328 to 1607° F
-200 to 875° C
986/RTD

 * These Input Types can be set for 0.1° display. If temperature goes above 999.9° or less than -199.9° the display will return to whole degree resolution.

How To Order

Specify part number from chart below:

Features

Using 2500 Series Using 2600 Series
Single Set Point, Type J 25013-986/J 26030-986/J
Single Set Point, Type K 25013-986/K 26030-986/K
Single Set Point, 3-Wire RTD 25023-986/RTD 26030-986/RTD
Single Set Point with Alarm, Type J 25113-986/J 26130-986/J
Single Set Point with Alarm, Type K 25113-986/K 26130-986/K
Single Set Point with Alarm, 3-Wire RTD 25123-986/RTD 26130-986/RTD
Dual Set Point, Type J Not Available 26033-986/J
Dual Set Point, Type K Not Available 26033-986/K
Dual Set Point, Type 3-Wire RTD Not Available 26033-986/RTD
Dual Set Point with Alarm, Type J Not Available 26133-986/J
Dual Set Point with Alarm, Type K Not Available 26133-986/K
Dual Set Point with Alarm, 3-Wire RTD Not Available 26133-986/RTD



HOW TO ORDER:

25013-986/J: Portable Temperature Process Controller, Single Set Point, Type-J, 10A 120VAC Outlet...$500.00

986 Series Instruction and Operation Manual


ACCESSORIES:

461-0004: 30Amp Fuse...$60.00


How To Place your ORDER



[ HOME | PRODUCTS | HANNA | MILWAUKEE | RO / DI | LAMOTTE | LOVE CONTROLS | DATA ACQUISITION MODULES | MONITORING & CONTROL SYSTEMS | TECHNICAL INFO | SALES | ABOUT US | ]