The 16A Series temperature / process controls set a new standard in 1/16 DIN power, flexibility, and value. This family of controls offers family interchangeability with different levels of features.

The 16A2 offers universal input (10 thermocouple types, 4 RTD types, voltage, and current), single or dual set point, alarm (optional), Fuzzy Logic, Self Tune, Peak / Valley indication, Per Cent Output indication, and Heater Break protection.

The 16A3 adds to this impressive list Auto / Manual capability, and 16 Segment Ramp and Soak with adjustable time base.

Options for the 16A2 and 16A3 include Process Output Retransmission (Voltage or Current), Remote Analog Set Point (Voltage, Current, Resistance), RS-232 Serial Communication, RS-485 Serial Communication, and 4-Stage Set Point.

Designed and built in the USA, the 16A family of controls offers the highest levels of features, function, and quality available today.

Features Include

  • Self Tune
  • Fuzzy Logic
  • Universal Input
  • Isolated Outputs
  • Loop Break Protection
  • Peak / Valley Indication
  • Percent Output Indication
  • Illuminated Keypad
  • Ramp / Soak Function (16A3)
  • Auto / Manual Station Function (16A3)

Specifications

  • Selectable Inputs: Thermocouple, RTD, DC Voltage, or DC Current selectable.
  • Input Impedance: Thermocouple = 3 megohms minimum. RTD current = 200 µA.
  • Current = 10 ohms. Voltage = 5000 ohms.
  • Sensor Break Protection: User determines control output to protect system after customer set time.
  • Set Point Range: Selectable (See Range Chart, previous page).
  • Display: Two 4 digit, 7 segment 0.30" high LEDs.
  • Control Action: Reverse (usually heating), Direct (usually cooling) selectable.
  • Proportional Band: 1 to 9999 °F, °C, or counts.
  • Reset Time (Integral): Off or 0.1 to 99.9 minutes.
  • Rate Time (Derivative): Off or 0.01 to 99.99 minutes.
  • Cycle Rate: 1 to 80 seconds.
  • On - Off Differential: Adjustable 1° F, 1° C, or 1 count to full scale in 1° F, 1° C, or 1 count steps.
  • Alarm On - Off Differential: 1° F, 1° C, or 1 count.
  • Fuzzy Intensity: 0 to 100%.
  • Fuzzy Rate: Off or 0.01 to 99.99 minutes.
  • Fuzzy Band: Off or 1 to 4000 °F, °C, or counts.
  • Accuracy: ±0.25% of span, ±1 least significant digit.
  • Resolution: 1 degree or 0.1 degree, selectable.
  • Line Voltage Stability: ±0.05% over the supply voltage range.
  • Temperature Stability: 4µV/°C (2.3 µV/°F) typical, 8 µV/°C (4.5 µV°F) maximum (100 ppm / °C typical,
  • 200 ppm / °C maximum).
  • Common Mode Rejection: 140 db minimum at 60 Hz.
  • Normal Mode Rejection: 65 db typical, 60 db at 60 Hz.
  • Isolation: Relay and SSR outputs: 1500 VAC to all other inputs and outputs.
  • SP1 and SP2 Current outputs: 500 VAC to all other inputs and outputs, but not isolated from each other.
  • SP1 and SP2 Switched Voltage outputs: 500 VAC to all other inputs and outputs, but not isolated from each other.
  • Process Output (Options 934, 936): 500 VAC to all other inputs and outputs.
  • Supply Voltage: 100 to 240 VAC, nominal., +10 -15%, 50 to 400 Hz. single phase; 132 to 240 VDC, nominal., +10 -20%.
  • Power Consumption: 5VA maximum.
  • Operating Temperature: -10 to +55 °C (+14 to 131 °F).
  • Storage Temperature: -40 to +80 °C (-40 to 176 °F).
  • Humidity Conditions: 0 to 90% up to 40 °C non-condensing 10 to 50% at 55 °C non-condensing.
  • Memory Backup: Nonvolatile memory. No batteries required.
  • Control Output Ratings:
  • SSR: 2.0 A combined outputs A & B @ 240 VAC at 25 °C (77°F). Derates to 1.0 A @ 55° C (130°F).
  • Relay: SPDT, 3 A @ 240 VAC resistive; 1.5 A @ 240 VAC inductive;Pilot Duty Rating: 250 VA, 2 A
  • @ 120 VAC or 1 A @ 240 VAC.
  • Alarm Relay: SPST, 3 A @ 240 VAC resistive; 1.5 A @ 240 VAC inductive; Pilot Duty Rating: 240
  • VA, 2 A @ 120 VAC or 1 A @ 240 VAC.
  • Current (isolated): 0 to 20 mA across 600 ohms maximum.
  • Switched Voltage (isolated): 15 VDC @ 20 mA.
  • Panel Cutout: 45 mm x 45 mm (1.775" x 1.775").
  • Depth Behind Mounting Surface: 115.3 mm (4.54").
  • Weight: 227 g (8 oz).
  • Agency Approvals: Pending.
  • Front Panel Rating: Type 4X, (IP65).

Input Ranges

INPUT TYPE RANGE °F RANGE °C
T/C, J*, Iron/ Constantan -100 to 1600 -73 to 871
T/C, K* -200 to 2500 -129 to 1371
T/C, E* -100 to 1800 -73 to 982
T/C, T*, Copper/ Constantan -350 to 750 -212 to 398
T/C, L*, Iron/ Konstantan (DIN) -100 to 1600 -73 to 871
T/C, N*, Nickel Chromium/ Nickel Silicon Chromium -100 to 2372 -73 to 1300
T/C, R, Platinum 13% Rhodium/ Platinum -0 to 3200 -17 to 1760
T/C, S, Platinum 10% Rhodium/ Platinum 0 to 3200 -17 to 1760
T/C, B, Platinum 6% Rhodium/ Platinum 75 to 3308 24 to 1820
T/C, C, Tungsten 5% Renium/ Tungsten 26% Renium 0 to 4208 -17 to 2320
RTD, 100 Ohm Platinum, 0.00392 Ohms/Ohm/°C * -328 to 1607 -200 to 875
RTD, 120 Ohm Nickel, 0.006725 Ohms/Ohm/°C * -112 to 608 -80 to 320
RTD, 100 Ohm Platinum, 0.00385 Ohms/Ohm/°C * -328 to 1607 -200 to 875
RTD, 1000 Ohm Platinum. 0.00385 Ohms/Ohm/°C * -328 to 1607 -200 to 875

* These Input Types can be set for 0.1° display. If temperature goes above 999.9° or less than -199.9° the display will return to whole degree resolution. 

The 0 to 20 mADC, 4 to 20 mADC, 0 to 10 VDC, 2 to 10 VDC, and -10 to +10 mVDC inputs are fully scalable from a minimum of 100 counts span placed anywhere within the range of -1999 to +9999. Decimal point position is adjustable from the zero place (9999), tenths (999.9), hundredths (99.99), or thousandths (9.999).

How To Order

To order, specify part number by filling the boxes with the appropriate numbers. If no options are desired, leave those boxes blank.

Options:
924 Analog Remote Set Point, 0 to 10 VDC. 
926 Analog Remote Set Point, 4 to 20 mADC. 
928 Analog Remote Set Point, 0 to 10,000 ohms.
934 Analog Retransmission of Process Variable or Set Variable, 4 to 20 mADC.
936 Analog Retransmission of Process Variable or Set Variable, 0 to 10 VDC.
948 4-Stage Set Point. One of four pre-set set point values can be implemented via contact closure.
949 4-Stage Set Point. One of four pre-set set point values can be implemented via contact closure. (Use this number instead of 948 when combining with 934, 936, or 992.)
992* RS-485 Serial Communications. Allows remote computer to read and write all control parameters.
993* RS-232 Serial Communications. Allows remote computer to read and write all control parameters.
* Protocol Information for Options 992 & 993.
9502 Operation on 12/24 VAC/VDC power.
Note: Remote Set Point Options (924, 926, 928) may not be combined with Retransmission Options or Serial Communications Options (934, 936, 992, 993).  4-Stage Set Point Option may only be combined with Retransmission Options (934, 936) or RS-485 Series Communications Option (992).